Ravel 2 Zone Fire Alarm system

Ravel 2 Zone Fire Alarm system

Ravel 2 Zone Fire Alarm system

  • Product Code : Ravel 2 Zone Fire Alarm system
  • Availability : In Stock
  • ₹ 8,990.00

  • Ex Tax :₹ 8,990.00

Product Overview

RE-102 / RE-104 is a right blend of affordability design, user friendly, latest technology and quality for fire alarm panels. RE - 102 / RE - 104, microprocessor based conventional Fire Alarm Control panel, are designed to be used for small size commercial buildings and small scale industries. The RE - 102 / RE - 104 models are 2 zone and 4 zone standalone panels respectively, with optional zone wise Sounder / Contact.

Special Features

  • Ravel Indian Manufacturer, International standard.
  • Switch Mode Power Supply.
  • Modular Construction, Serviceable.
  • Surface Mount Technology.
  • Battery polarity & deep discharge protection.

Features

  • Ravel Indian Manufacturer, International standard.
  • Switch Mode Power Supply.
  • Modular Construction, Serviceable.
  • Surface Mount Technology.
  • Battery polarity & deep discharge protection.
  • As per IS -15908: 2011 Standard.
  • 16 X 2 Dot Matrix LCD Display.
  • Standby battery backup with built in charging.
  • Fire / Fault status in unambiguous colored LED indication.
  • Switch Mode Power Supply.
  • Tactile Keypad for easy panel operation.
  • System on indication.
  • Main, Standby status indication.
  • Low Battery visual warning with audible tone.
  • Relay output for actuators for Fire and Fault.
  • Lamp Test facility
  • Zone wise one man walk Test Facility.
  • Zone wise Isolation facility with loop voltage cut off.
  • Compatible to all type of Conventional Detectors.
  • Optional Zone Wise Sounder / Zone Wise Contact.

Electrical Specification

Primary Power

    120 - 220VAC , 50 Hz

Standby Power

    24V D.C (2 Nos of 12v, 7Ah Sealed Lead acid battery).

    Quiescent current : 55mA

Operating Condition

    Operating Temperature 0 - 49° C/32-120° F.

    Relative Humidity 93 ± 2% RH (noncondensing) at 32 ±2° C/90 ±3° F.

Charging Circuit

        Charging Voltage 28.2V, ±0.5V

        Charging Current 0.5 A (Max.).

Notification Appliance Circuits

    Class B wiring

    Operating Nominal Voltage: 24VDC

    Current for NACs : 0.6 Amp

    End-Of-Line Resistor : 4K7, 1/4 watt

Common Relays

Type

Form C

No of Relays

3

Relay Contact Rating

2Amps @ 30 VDC, 0.5Amps @125VAC.

Power Factor

1

Initiating Device Circuits (Zone Circuit)

All zones are Class B wiring Normal Operating Voltage

14- 21 VDC

Alarm Current

 15 - 30mA

Short Circuit Current

42mA Maximum

Loop resistance

50 ohms Maximum

End-Of-Line Resistor

4.7K, 1/4watt

Standby Current

 6.8mA (2.4mA for Detectors)


Mounting Details    

             

Mechanical Specification

Dimensions

(350W X 250H X 100D)

Color 

Red / White

Construction

18 Gauge (1.22mm) CRCA sheet with powder-coated Finish

IP Rating 

 IP50

Cable Entry

11xø19mm Knockout in top of the cabinet


Wiring Diagram


Ordering Information:

MODEL

DESCRIPTION

RE-102-W
2 ZONE Fire Alarm Panel
RE-102-R
2 ZONE Fire Alarm Panel
RE-102-W
4 ZONE Fire Alarm Panel
RE-102-R
4 ZONE Fire Alarm Panel

Compatible Devices

MODELS

DESCRIPTION

RE-316S-2L
Photoelectric Smoke detector with base.
RE-316H-2L
Heat detector with base.
RE-316SH-2L
Photoelectric & Heat detector with base





Write a review

Note: HTML is not translated!
    Bad           Good